ABC cable assembled to SANS 1418 – safe, compact, and reliable.
Insulated wire bundles ideal for overhead low-voltage networks.
Durable XLPE insulation for African climate conditions.
ABC Cable – Engineered for utility-grade performance.
Preassembled overhead cable bundles for fast, efficient installation.

Application

 

Assembling insulated wire bundles, also known as Aerial Bundled Cables (ABC), are designed for low-voltage overhead power distribution in compliance with SANS 1418, the South African national standard. These cables offer a safe, efficient, and compact alternative to traditional bare conductor systems, particularly suited to high-density urban, peri-urban, and informal settlement environments.

The standard configuration includes three XLPE-insulated aluminum phase conductors and one bare or insulated neutral messenger, bundled together to form a lightweight, self-supporting unit. Optional public lighting conductors can also be included depending on system design.


Thanks to the full insulation of live conductors, ABC cables minimize the risk of electric shock, phase-to-phase faults, and outages due to vegetation or external contact. The bundled design supports reduced pole spacing, simplified installation, and lower right-of-way requirements—ideal for areas with limited space or safety challenges.

With XLPE insulation rated for 90°C continuous operation, UV and weather resi

CONSTRUCTION

000 0000

• Phase Conductor: Stranded,Circular compacted,Circular compressed AAC.
• Neutral Conductor: Stranded,Circular compacted or uncompacted AAAC.
• Street Lighting Conductor: Stranded,Circular compacted,Circular compressed AAC.
• Insulation: Cross-linked polyethylene (XLPE),Black color,Weather and UV resistant.

CHARACTERISTICS

 

Category Technical Description Typical Applications
   Standard SANS 1418 – South African National Standard for Low-Voltage Aerial Bundled Cables (typically 0.6/1 kV) Widely used in South Africa, Botswana, Namibia, and other SADC countries for overhead distribution
   Cable Type Assembled Insulated Wire Bundle (ABC)Conductors bundled together and helically twisted around a neutral/messenger wire Ideal for urban electrification, rural grid extension, and municipal street lighting
   Voltage Rating 0.6/1 kV – for low-voltage distribution networks Suitable for residential feeders, public area grids, informal settlements, and commercial low-voltage supply
   Conductor Material 1350-H19 stranded aluminum for phase conductors- Alloy or steel-reinforced aluminum (ACSR / AAAC) for neutral/messenger Combines lightweight with high conductivity and strength
   Insulation XLPE (Cross-linked Polyethylene)– UV-resistant, weatherproof, flame-retardant Ensures durability in sunny, humid, windy, and dusty African environments
   Assembly Configuration 3 or 4-core bundle:• 3 × Phase + 1 × Neutral• Optional public lighting core (e.g. 3 × Phase + 1 × Neutral + 1 × Lighting) Enables single-phase, three-phase, or mixed-load distribution from a single compact overhead bundle

STANDARD

SANS 1418
AAC ICEA S-76-474
AAAC ICEA S-76-474
ACSR ICEA S-76-474

Type of conductor or core Nominal cross-sectional area mm2 Number of wires  mm Resistance at 20C
Ω/km
Max
Diamater of conductor
mm
Min
Diamater of conductor mm Max Breaking force Min Thickness of dielectric mm Average Thickness of dielectric mm Min  core Outside diameter mm Min core Outside diameter mm Max
Phase or auxiliary or nonstrain- bearing neutral(aluminium) 16 6 1.91 4.6 5.1 2070 1.2 0.98 7 7.8
25 6 1.2 5.8 6.3 3300 1.4 1.16 8.6 9.4
35 6 0.868 6.8 7.3 4500 1.6 1.34 10 10.9
50 6 0.641 7.9 8.4 6200 1.6 1.34 11.1 12
70 12 0.443 9.7 10.2 8900 1.8 1.52 13.3 14.2
95 15 0.32 11 12 12300 1.8 1.52 14.6 16
120 15 0.253 12.5 13.5 15600 1.8 1.52 16.3 17.5
150 15 0.206 13.9 15 19200 1.8 1.52 17.1 18.6
              1.52    
Service connection (aluminium) 16         25 6            6 1.91   1.2   1.83 1.15 0.727 4.6 5.6 2070     3300 1.2     1.4 0.98      1.16 7.0         8.6 8.0        9.6
Service connection (copper) 10 6 1.83 _ 4.2 3600 1.2 0.98 6.2 7
15 6 1.15 _ 5.3 5700 1.2 0.98 7.2 8
25 6 0.727 _ 6.6 8750 1.4 1.16 8.6 9.6
Supporting (aluminium) 54.6 7*3.15 0.63 9.2 9.6 16600 1.6 1.34 12.3 13
70 7*3.50 0.5 10 10.4 20100 1.6 1.34 12.9 13.6
AAC Conductor Supported Service Drop Cable- ICEA S-76-474
Code Name Size Al Phase Core AAAC Conductor Rated Strength Approx. Overall Dia. Approx. Weight
Cross-section Area Str. No. Dia. Insulation Nominal Cross-section Area Str. No. Dia.
Thickness
AWG/MCM mm2 No.s mm mm mm2 No.s mm KN mm kg/km
DUPLEX
Collie 1X6+6AWG 13.3 7 4.65 1.14 13.3 7 4.68 2.5 11.6 92
Spaniel 1X4+4AWG 21.15 7 5.7 1.14 21.15 7 5.88 3.9 13.8 138.3
Doberman 1X2+2AWG 33.62 7 7.2 1.14 33.63 7 7.41 6 16.8 211.2
Malemute 1X1/0+1/0AWG 53.5 19 9.2 1.52 53.51 7 9.36 8.8 21.6 339.9
TRIPLEX
Patella 2X6+6AWG 13.3 7 4.65 1.14 13.3 7 4.68 2.5 13.3 149
Oyster 2X4+4AWG 21.15 7 5.7 1.14 21.15 7 5.88 3.9 15.6 221
Clam 2X2+2AWG 33.62 7 7.2 1.14 33.63 7 7.41 6 18.9 334
Murex 2X1/0+1/0AWG 53.49 7 9.2 1.52 53.51 7 9.36 8.8 24.2 538
Nassa 2X2/0+2/0AWG 67.43 7 10.3 1.52 67.44 7 10.5 11.2 26.6 663
Melita 2X3/0+3/0AWG 85.01 19 11.6 1.52 85.03 7 11.79 14.7 29.4 820
Portunus 2X4/0+4/0AWG 107.2 19 13 1.52 107.2 7 13.26 17.9 32.5 1017
Nannynose 2X336.4+336.4MCM 170.45 19 16.56 2.03 170.46 19 16.9 27.3 41.7 1631
QUADRUPLEX
Pinto 3X4+4AWG 21.15 7 5.7 1.14 21.15 7 5.88 3.9 18 302
Mustang 3X2+2AWG 33.62 7 7.2 1.14 33.63 7 7.41 6 21.6 454
Criollo 3X1/0+1/0AWG 53.51 19 9.2 1.52 53.51 7 9.36 8.8 27.8 734
Percheron 3X2/0+2/0AWG 67.44 19 10.3 1.52 67.44 7 10.5 11.2 30.4 902
Hanoverian 3X3/0G+3/0AWG 85.03 19 11.6 1.52 85.03 7 11.79 14.7 33.6 1113
Oldenburg 3X4/0+4/0AWG 107.2 19 13 1.52 107.2 7 13.26 17.9 37 1377
Lippizaner 3X336.4+336.4MCM 170.46 19 16.56 2.03 170.46 19 16.9 27.3 47.5 2212

 

AAAC Conductor Supported Service Drop Cable- ICEA S-76-474
Code Name Size Al   Phase Core AAAC   Conductor Rated Strength Approx.Overall Dia. Approx.Weight
Cross-section Area Str. Dia. Insulation   Nominal Cross-section   Area Stranding No. Dia.
No. Thickness
AWG/MCM mm2 No.s mm mm mm2 No.s mm KN mm kg/km
Duplex
Chihuahua 1X6AWG+6AWG 13.3 1 4.11 1.14 15.5 7 5.04 4.93 11.43 96
Vizsla 1X6AWG+6AWG 13.3 7 4.65 1.14 15.5 7 5.04 4.93 11.97 98
Harrier 1X4AWG+4AWG 21.15 1 5.19 1.14 24.67 7 6.36 7.82 13.83 146
Whippet 1X4AWG+4AWG 21.15 7 5.7 1.14 24.67 7 6.36 7.82 14.34 148
Schnauzer 1X2AWG+2AWG 33.62 7 7.2 1.14 39.25 7 8.02 12.45 17.5 226
Heeler 1X1/0AWG+1/0AWG 53.49 19 9.2 1.52 62.48 7 10.1 19.83 22.35 364
Triplex
Hippa 2X6AWG+30.58MCM 13.3 7 4.66 1.14 15.5 7 5.04 4.93 13.58 154
Bamacle 2X4AWG+48.69MCM 21.15 7 5.7 1.14 24.67 7 6.36 7.82 16.03 230
Shrimp 2X2AWG+77.47MCM 33.62 7 7.2 1.14 39.25 7 8.01 12.45 19.36 349
Gammarus 2X1/0AWG+123.3MCM 53.51 7 9.2 1.52 62.48 7 10.11 19.83 24.84 562
Cyclops 2X2/0AWG+155.4MCM 67.44 19 10.3 1.52 78.74 7 11.34 23.96 27.3 693
Flustra 2X3/0AWG+195.7MCM 85.03 19 11.6 1.52 99.16 7 12.75 30.18 30.18 858
Lepas 2X4/0AWG+246.9MCM 107.22 19 13 1.52 125.11 7 14.31 38.05 33.31 1064
Crab 2X4AWG+30.58MCM 21.15 7 5.7 1.14 15.5 7 5.04 4.93 15.08 205
Solaster 2X2AWG+48.69MCM 33.62 7 7.2 1.14 24.67 7 6.36 7.82 18.18 309
Sandcrab 2X1/0AWG+77.47MCM 53.51 7 9.2 1.52 39.25 7 8.01 12.45 23.33 498
Sipho 2X2/0AWG+97.65MCM 67.44 19 10.3 1.52 49.48 7 9 15.69 25.62 613
Fulgar 2X3/0AWG+123.3MCM 85.03 19 11.6 1.52 62.48 7 10.11 19.83 28.28 757
Arca 2X4/0AWG+155.4AWG 107.22 19 13 1.52 78.74 7 11.34 23.96 31.18 936
QUADRUPLEX
French Coach 3X6AWG+30.58MCM 13.3 7 4.66 1.14 15.5 7 5.04 4.93426 15.61 211
Arabian 3X4AWG+48.69MCM 21.15 7 5.7 1.14 24.67 7 6.36 7.82369 18.29 312
Belgian 3X2AWG+77.47MCM 33.62 7 7.2 1.14 39.25 7 8.01 12.4468 22 469
Shetland 3X1/0AWG+123.3MCM 53.51 19 9.2 1.52 62.48 7 10.11 19.8259 28.26 757
Thoroughbred 3X2/0AWG+155.4MCM 67.44 19 10.3 1.52 78.74 7 11.34 23.9601 31 932
Trotter 3X3/0AWG+195.7MCM 85.03 19 11.6 1.52 99.16 7 12.75 30.1835 34.2 1151
Walking 3X4/0AWG+246.9MCM 107.2 19 13 1.52 125.1 7 14.31 38.0516 37.68 1424
ACSR Conductor Supported Service Drop Cable- ICEA S-76-474
Code Name Size Al Phase Core ACSR Messenger
Cross-section Area Str. No. Dia. Insulation Nominal Thickness Cross-section Area Al Wire St Wire Stranded Dia.
Str. Dia. Str. No. Dia.
No.
AWG/MCM mm2 No.s mm mm mm2 No.s mm No.s mm mm
DUPLEX                      
Shepherd 1X6+6 13.3 7 4.68 1.14 13.3 6 1.68 1 1.68 5.04
Terrier 1X4+4 21.1 7 5.7 1.14 21.15 6 2.12 1 2.12 6.36
Chow 1X2+2 33.6 7 7.2 1.14 33.62 6 2.67 1 2.67 8.01
Bull 1X1/0+1/0 53.5 19 9.2 1.52 53.51 6 3.37 1 3.37 10.11
TRIPLEX                      
Voluta 2X6+6 13.3 7 4.66 1.14 13.3 6 1.68 1 1.68 5.04
Periwinkle 2X4+4 21.1 7 5.7 1.14 21.15 6 2.12 1 2.12 6.36
Conch 2X2+6 33.6 7 7.2 1.14 13.3 6 2.67 1 2.67 8.01
Neritina 2X1/0+1/0 53.5 7 9.2 1.52 53.51 6 3.37 1 3.34 10.02
Triton 2X2/0+2/0 67.4 19 10.3 1.52 67.44 6 3.78 1 3.78 11.34
Mursia 2X3/0+3/0 85 19 11.6 1.52 85.03 6 4.25 1 4.25 12.75
Zuzara 2X4/0+4/0 107.2 19 13 1.52 107.22 6 4.77 1 4.77 14.31
Limpet 2X336.4+336.4 170.4 19 16.56 2.03 170.46 18 3.47 1 3.47 17.35
Strombus 2X4+6 21.1 7 5.7 1.14 13.3 6 1.68 1 1.68 5.04
Cockle 2X2+4 33.6 7 7.2 1.14 21.15 6 2.12 1 2.12 6.36
Janthina 2X1/0+2 53.5 7 9.2 1.52 33.62 6 2.67 1 2.67 8.01
Ranella 2X1/0+2 53.5 19 9.2 1.52 33.62 6 2.67 1 2.67 8.01
Clio 2X2/0+1 67.4 19 10.3 1.52 42.41 6 3 1 3 9
Aega 2X3/0+1/0 85 19 11.6 1.52 53.51 6 3.37 1 3.37 10.11
Cerapus 2X4/0+2/0 107.2 19 13 1.52 67.44 6 3.78 1 3.78 11.34
Cowry 2X336.4+4/0 170.4 19 16.59 2.03 107.22 6 4.77 1 4.77 14.31
QUADRUPLEX                      
Chola 3X6+6 13.3 7 4.66 1.14 13.3 6 1.68 1 1.68 5.04
Hackney 3X4+4 21.1 7 5.7 1.14 21.15 6 2.12 1 2.12 6.36
Pallomino 3X2+2 33.6 7 7.2 1.14 33.62 6 2.67 1 2.67 8.01
Costena 3X1/0+1/0 53.5 19 9.2 1.52 53.51 6 3.37 1 3.37 10.11
Grullo 3X2/0+2/0 67.4 19 10.3 1.52 67.44 6 3.78 1 3.78 11.34
Suffolk 3X3/0+3/0 85 19 11.6 1.52 85.03 6 4.25 1 4.25 12.75
Appaloosa 3X4/0+4/0 107.2 19 13 1.52 107.22 6 4.77 1 4.77 14.31
Gelding 3X336.4+4/0 170.4 19 16.56 2.03 107.22 6 4.77 1 4.77 14.31