| Aspect |
Details & Applications |
| Conductor Material |
Annealed copper or aluminum, solid or stranded, per IEC 60228 / ASTM B8 |
| Insulation Material |
XLPE (Cross-linked Polyethylene) or EPR (Ethylene Propylene Rubber) – for high dielectric strength and thermal stability |
| Insulation Grade |
100% level: For systems with effectively grounded neutral133% level: For systems with ungrounded or intermittently grounded neutral |
| Voltage Range |
Typically from 5 kV to 35 kV |
| Cable Type |
Unarmoured or armoured, with metallic shield (copper tape or wire) |
| Sheath Material |
LDPE or LSZH (Low Smoke Zero Halogen) – protects against UV, chemicals, and mechanical damage |
| Standards |
ICEA S-93-639 (NEMA WC74), ICEA S-97-682, IEEE 383, IEC 60502-2, AEIC CS8 |
| Electrical Properties |
High dielectric strength, low partial discharge, stable under long-term loading |
| Temperature Rating |
90°C continuous operation; up to 250°C in short circuit (5 sec) |
| Shielding |
Metallic shield ensures proper fault current path and controls electric field |
| Typical Applications |
Power distribution in utilities, industrial zones, substations- Installed in duct banks, conduits, direct buried or trays |
| Selection Tip |
Use 100% insulation for grounded systems (more economical)Use 133% insulation where fault clearance may be delayed |